Search

 
 

Inverter ACTIVE CUBE

 

Power Range (ACU210)
0.25 ... 9.2 kW / 1- or 3-ph 200 - 240 V / 50 - 60 Hz (±10%)

Power Range (ACU410)

0.25 ... 400 kW (1200 kW in parallel connection)
3-phase 360 - 480 V / 50 - 60 Hz (± 10%)

Power Range (ACU610)
160 - 400 kW */ three-phase 690 V / 50 Hz - 60 Hz (± 10%)
*1200 kW in parallel connection

Type of Control
Vector sensor less and closed loop control for Permanent Magnets, Induction and Synchronous Reluctance machines.

Overload Capacity
150% for 60 seconds and 200% for 1 second

Switching Frequency
2, 4, 8, 12, 16 kHz

Enclosure
IP20 (EN 60529)

EMC Filter
Integrated up to 9.2 kW (EN 61800-3)

Main Standard Hardware features
• Integrated safe torque off (STO Sil 2) function
• External 24Vdc supply
• Integrated dynamic braking module
• DC link connection
• Various feedback sensors

Optional Expansion Modules
Expansion of analog, digital inputs and outputs, additional encoder or resolver input and sincos encoder, repetition frequency output, System bus

Optional Communication Modules
PROFIBUS-DPV1, CANopen, RS232, RS485, DeviceNet, EtherCAT®, PROFINET, VABus/TCP, Modbus TCP, EtherNet I/P


Optional Keypad
Removable keypad KP500 with copy function, Cabinet mounting kit and handheld for keypad

PC Software VPlus
• Windows-based engineering “workbench” with easy interface
• Drive parameters set-up
• Scope function
• Teleservice

Main Software Features
• Positioning function
• Rotary table control
• Master / Slave function with electronic gear
• Power failure regulation
• Function for lift, crane and winch applications
• Spindle control up to 1000Hz
• Traverse function for winders
• Volume flow control
 